Connecting a Controller (Master) to a WAGO Device (Slave) (2024)

In what follows, you connect a 750-8216 Controller (EtherNet/IP scanner as master) with a 750-363 Fieldbus Coupler (EtherNet/IP adapter as slave).

The 750-8216 Controller is used here as an example. Another PFC200 second-generation controller, an edge controller or a touch panel can also be used here (see supported devices under WAGO Devices as EtherNet/IP Masters (License Required)).
Instead of the 750-363 Fieldbus Coupler (and its variants), EtherNet/IP devices of the WAGO I/O System Field can also be used, for example (see supported devices in WAGO Devices as EtherNet/IP Slaves).

The 750-363 Fieldbus Coupler is already integrated into the product catalog via an EDS file.

Connecting a Controller (Master) to a WAGO Device (Slave) (1) Note

Connect EtherNet/IP devices to port X1 of the controller!

Always connect EtherNet/IP devices to port X1 of the controller. Only this port is used for EtherNet/IP communication.

Place Devices on the Communication View

  1. Select the controller and fieldbus coupler from the product catalog and use the mouse to drag them into the Network view (communication layer).
Connecting a Controller (Master) to a WAGO Device (Slave) (2)

Configure I/O Modules Used in the Device Detail View

  1. Open the Device Detail view (in either graphical and tabular view) by double-clicking the fieldbus coupler.
  2. Note: If you do not see a graphical node view for the WAGO fieldbus coupler, you are not using the current version of the device, but an outdated version (marked as “deprecated” in the product catalog and in the tool tip for the device). Although the device is fully functional, input/output data must be created manually. Newer WAGO fieldbus couplers automatically generate input/output data from the node configuration. If you want to switch to a new version, delete the old device from your project and add a new one. Please note that any existing mapping in the fieldbus configurator must also be recreated in this case.
  3. Arrange the I/O modules used analogously to your hardware by dragging them from the product catalog and positioning them after the device.
  4. Parameterize the I/O modules as needed by selecting them and making changes on the “Settings” panel for each.
  5. Note: If you change the operating modes / process image lengths / mailbox sizes for an I/O module, click once on the “Input/Output data" tab after the configuration to update the display for the byte sizes of input/output data points.
  6. Go back to the Network view.
  7. Proceed in the same way with the second device.

Connect Devices

  1. Click the gray connector (Ethernet/IP) for one of the devices in the Network view (communication layer) and hold down the mouse button.
  2. To connect the devices to each other, drag the connection line to the same type connector on the second device. Release the mouse button as soon as a green plus sign appears.
  3. Connecting a Controller (Master) to a WAGO Device (Slave) (3)
  4. The devices are connected. The arrow of the connection line indicates the automatically assigned roles of the device: The connection line starts at the master and ends at the slave.
  5. A yellow warning symbol in the device tile of the master indicates that a license is required to use the EtherNet/IP functionality.
  6. Connecting a Controller (Master) to a WAGO Device (Slave) (4)
  7. You can run the device without a license for 30 days in evaluation mode. Otherwise, follow the steps below.

Use License for EtherNet/IP Master

  1. If you have already purchased a license, first enter it in e!co*ckPIT: Backstage View > “Licensing” page, [License Management] > [Enter Licenses].
  2. Once you have entered the license, open the “Available Licenses” and “Project Licensing” panels (via the ribbon > “VIEW” tab >[ Available Licenses] button and [Project Licensing]).
  3. Use the “Auto-assign everything” option on the “Project Licensing” panel (recommended).
    Alternatively, drag the license from the “Available Licenses” panel to the appropriate device on the “Project Licensing” panel, or drag the license directly onto the device in the Network view.
  4. Then load the license onto the device by synchronizing it (the [Synchronize] button on the DEVICE tab of the ribbon or on the “Project Licensing” panel).

Connecting a Controller (Master) to a WAGO Device (Slave) (5) Note

Information about licensing in the e!co*ckPIT product manual:

The e!co*ckPIT product manual describes in detail how licensing is handled. It describes how to acquire licenses, activate them, assign them to devices and link them in the device (see “Purchasing a License,” “Activating the License” and “Activating Runtime Licenses” in the e!co*ckPIT product manual).

Connecting a Controller (Master) to a WAGO Device (Slave) (6) Note

“WAGOupload” can be used for series commissioning

The “WAGOupload” software is available as an alternative for commissioning a larger number of controllers. This software can also be used to load licenses and projects onto controllers.

Make the Device Settings on the “Settings” Panel

You can change the settings or parameters of the devices that have been added on the “Settings” panel. The panel is open by default. If it is not, open it using the context menu of the device and the [Settings] button.

Connecting a Controller (Master) to a WAGO Device (Slave) (7)

The tabs, entry screens and selection fields on the “Settings” panel depend on the specific device. Which settings options are displayed depends on the content of the specific device description file.

Controller (Master):

  1. Select the controller (master) in the network view.
  2. First set the EtherNet/IP interface of the controller:
    On the “Device” tab of the “Settings” panel, enter the IP address of the controller.
    Note: This change requires the master to be offline.
  3. Connecting a Controller (Master) to a WAGO Device (Slave) (8)
  4. To load further data of the controller into e!co*ckPIT, click the [Settings] button on the same tab.
  5. The integrated “WAGO Ethernet Settings” tool opens.
  6. Wait until the controller configuration appears.
  7. Close “WAGO Ethernet Settings” again.
  8. Confirm the transfer of the configuration data to e!co*ckPIT with [Apply].
  9. The display is updated on the “Device” tab of the “Settings” control panel:
    For example, the MAC address of the controller now appears here.
    Note: EtherNet/IP uses only network interface X1 for communication.
Connecting a Controller (Master) to a WAGO Device (Slave) (9)

Note: The “EtherNet/IP” tab of the control panel also contains the IP address and MAC ID, but is for information only. Only the “Device” tab is used for making settings.

Fieldbus Coupler (Slave):

  1. Select the fieldbus coupler (slave) in the Network view.
  2. On the EtherNet/IP” tab of the “Settings” panel, you can see that the slave device already contains device information. This is type plate data from the EDS file. This data does not have to be modified.
  3. Connecting a Controller (Master) to a WAGO Device (Slave) (10)
  4. Enter the IP address of the slave.

Configure Slave

You configure the slave in the data point configurator.

  1. Open the data point configurator by double-clicking on the device tile of the slave.
  2. First start on the open “Connection” tab.
  3. This tab already contains entries. These concern Connections described in the EDS file and created with its predefined parameters.

Edit Connection:

  1. Select one of the connections and click the [Edit Connection] button.
  2. The “Edit Connection” dialog appears.
  3. Here you can change the name of the connection, for example.
  4. For example, for WAGO devices, you can specify which data of the connected I/O modules should be used for the connection under “Path”.
    For instance, you can select only the analog input modules.
  5. Confirm your changes with [OK].

Tip: The connection between input/output data points and handling via assembly instances is illustrated in the Example Configuration for Data Exchange with a WAGO EtherNet/IP Fieldbus Coupler 750-363.

Create Additional Connections (Optional):

  1. Create a new connection by clicking the [Add Connection] button.
  2. In the “Add Connection” dialog, specify the parameters of the connection (see “Connection” Tab).
  3. To create the connection, click [OK].
  4. The connection appears in the list.

Adjust Input/Output Data Points for Connections:

Note: For WAGO fieldbus couplers, input/output data are created and modified automatically based on the node structure. The input/output data points can only be created and modified as described below for generic connections that you have created yourself.

  1. Select the connection for which you want to view or edit input/output data points.
  2. The input/output data points for the selected connection are displayed on the “Input/Output Data” tab (if they are already predefined via the EDS), and the display is context-sensitive.
    If this is an “Exclusive Owner” connection, you see data points for inputs (T→O) and data points for outputs (O→T) here, for example.
  3. To modify entries directly in the table, double-click the respective fields.

Create New Input/Output Data Points (Optional, or for Connections You Have Created Yourself):

For modular devices and generic connections, you must create the input/output data points manually.
Note: Note which options the device offers, for example, which assemblies are supported. This information can be found in the corresponding product manual. Also note the node configuration used (I/O modules, number, type etc.).

  1. To create an input data point, right-click “Input (T → O)” and select [Add].
  2. To create an output data point, right-click “Output (O → T)” and select [Add].
  3. Tips: Alternatively, you can create multiple data points by selecting [Add multiple].
    If you want to create data points at a specific location in the data point list, then select Add/Add multiple in the context menu of one of the existing data points.
  4. If necessary, adjust the name, data type and bit size by double-clicking the relevant value of the input/output data point.
  5. If necessary, adjust the parameters for the input and output size of the connection.
  6. To apply the changes, click [Enter].

You have now defined the data points for the selected connection(s). The connections and data points are offered for selection in the fieldbus configurator for the controller.

Settings on the “Target Configuration” Tab:

Settings on the “Target Configuration” tab are not required for the 750-363 Fieldbus Coupler because they are not defined in the EDS file.
Other slave devices may have parameters here. You can then edit these further (see “Target Configuration” Tab).

Set User Parameters:

  1. Switch to the “User Parameters” tab.
  2. Parameters that are defined in the EDS file are displayed here. Only the “Failure Reaction” value is predefined for the 750-363 Fieldbus Coupler.
  3. In the “Failure Reaction” selection field, specify how the fieldbus coupler should react in the event of an error.
  4. Advanced setting: If necessary, you can create additional parameters. To do so, click Add in the context menu. However, this requires you to know the exact path and valid data types/values.
  5. To apply the parameter(s) for the device, click the corresponding checkbox in the “Write” column.
    Note: Note that writing only is performed if the “User Parameters” option is enabled in the fieldbus configurator on the “Communication Settings” Tab (enabled by default).
  1. The configuration of the slave is completed.

Configure Connection between Master and Slaves

You can configure the connection between the master and slaves in the fieldbus configurator. Here the connections configured in the slave are displayed with their data points and made available for the controller.

  1. Click the EtherNet/IP connector of one of the two connected devices.
  2. Open the EtherNet/IP fieldbus configurator by clicking the [Configurator] button.
  3. Connecting a Controller (Master) to a WAGO Device (Slave) (11)
  4. The fieldbus configurator opens. The connection is shown in the header section of the configurator. If multiple slaves are connected to one master, you can modify the selection under “Selected Connection.”
  5. The fieldbus configurator is divided into two columns:
    On the left side, the “Communication Connections” opens first; this shows the connections with the data points that are transferred via the bus from the slave to the master.
    The right side shows the connections available on the slave. In addition, the input/output data is displayed with the individual data points in a tree structure.
  6. For connections to be established by the master when connecting, use the mouse to drag the desired connections from the right section to the left section (“Communication Connections” tab). Alternatively, select Map in the context menu of the connection.
  7. Note: Connections are always provided as a whole with all data points for the master.
  8. Connecting a Controller (Master) to a WAGO Device (Slave) (12)

Configure Connection:

  1. To further configure the connection, click the [...] button to the left of the connection.
  2. The “Edit Connection” dialog opens.
  3. Connecting a Controller (Master) to a WAGO Device (Slave) (13)
  4. Make the settings according to Fieldbus Configurator – “Edit Connection” Dialog. Usually, no changes are required for the WAGO device.
  5. Click [OK].

Perform Mapping between Data Points and Program Variables:

  1. To map data points of the connection to program variables or to create new program variables by mapping, double-click within the relevant input field of the “Variable” column.
  2. Assign a name. For example, enter the variable “in” for the first input data point and the variable “out” for the first output data point.
  3. Connecting a Controller (Master) to a WAGO Device (Slave) (14)
  4. The mapping creates new global variables in the master application. This establishes the connection to the slave.
  5. Tip: The [...] button to the right of the variable field opens the input assistant. There, as an alternative, you can select program variables that already exist for the mapping.
  6. Note: Only program variables of data type BYTE can be mapped to input/output data points of data type BOOL.

Access Data Points

  1. Open the program structure and the main program of the master.
  2. Connecting a Controller (Master) to a WAGO Device (Slave) (15)
  3. Use the variables in your program.
    For example, create a variable “read” in your program that reads in the word from “in”: read:=in; and/or write a value to the variable “out”: out:=16#ABAB;
  4. Tip: Press the [F2] key to open the input assistant for easy variable selection.
  5. Connecting a Controller (Master) to a WAGO Device (Slave) (16)
  1. In this way, slave data points of an EtherNet/IP connection can be used for the master or in the program of the master.

Make Communication Settings

  1. Switch back to the fieldbus configurator.
  2. Open the “Communication Settings” tab.
  3. By default, the “Compatibility Check” option is selected here, which ensures that the slave performs a compatibility check for the type plate parameters. For the fieldbus coupler, this setting can be retained.
  4. You can find more information on how the compatibility check works in “Communication Settings” Tab.

Testing the Configuration

  1. Switch to the Network view and select the master.
  2. Click the [Connect] button in the ribbon.
  3. Confirm the message window for the parameter changes with [OK].
  4. Log in to the device.
    (For new WAGO devices where the access data has not been modified, use the username “admin” and password “wago”).
  5. The device is connected.
  6. Open the “PROGRAM” tab in the ribbon and click the [Start] button.
  7. The program is running. You can now test the connection and the data exchange in the fieldbus configurator or in the Web-Based Management of the controller:
  8. Testing in the Fieldbus Configurator:
    Open the “Communication Status” tab in the fieldbus configurator.
  9. Here you see the message “Adapter is running.”
    Note: If the status does not update automatically, click the [Acknowledge slave diagnosis] button.
  10. If the value shown is “NumDiagSlaves” = 0, all the slaves are configured correctly.
    If not, check whether the entered data types and sizes of the input/output data points of the connection match the data sizes of connected I/O modules.
  11. Testing the Configuration in Web-Based Management:
    Note: Note that only WAGO devices have Web-Based Management.
    Open the Web-Based-Management of the master by entering the IP address in a browser window.
    Open the “I/O Data” page in the Web-Based Management.
  12. Here you can see all input and output channels with the values that you have specified in the program or that were read in.

Connecting a Controller (Master) to a WAGO Device (Slave) (17) Note

Check WBM settings if EtherNet/IP communication fails

If no EtherNet/IP communication is possible, check whether the “Enable Binary Padding” function is deactivated in the WBM on the “EtherNet/IP” page of the fieldbus coupler (default setting). Only then is communication via EtherNet/IP possible. If, on the other hand, “Enable Binary Padding” is enabled, the assembly instances 101 to 109 are padded to an even number of bytes. This means that the byte size to be transmitted does not match that expected by the fieldbus coupler, so the communication is aborted.

Also check the header configuration set in the WBM: Only “Originator to Target” is activated for “RUN/IDLE Header”. Do not change these settings, otherwise the connection will be aborted, since the header information is already defined by the EDS of the device.

Connecting a Controller (Master) to a WAGO Device (Slave) (2024)

FAQs

What is the default password for the Wago controller? ›

Open the WAGO's web server (default: 192.168. 2.1) and log in. Default username: root. Default password: wago.

How to connect PS4 controller to PS4 without another controller? ›

How to pair your controller with your PS5 console or PS4 console
  1. Make sure that your console is on.
  2. Connect the controller to your console using the included USB cable.
  3. If your controller is turned off, press the PS button. After the light bar blinks, the player indicator lights up.

What is the default password for wago 750 352? ›

Log on as the administrator with the user name “admin” and the password “wago”.

What is the root password for wago pfc100? ›

8.1) User accounts (usr/pwd):
UserPassword
rootwago
adminwago
useruser

How do I connect my DualShock 4 to my PS4 without wire? ›

Press and hold the PlayStation button for 3 seconds. Press and hold the 'Share' button, above the arrow buttons, and the PlayStation button at the same time. The light bar should blink now. Select your controller in the Bluetooth window of your PlayStation.

How do I connect my PS4 controller to my computer without the cord? ›

With the DualShock 4 turned off (you'll know by the deactivated light bar), press and hold the PlayStation and Share buttons for three seconds until the light bar starts double flashing. Access the Bluetooth menu on your PC via the system tray. Click "Add Bluetooth or other device." Click "Bluetooth."

Can you connect a PS4 controller to a switch without an adapter? ›

You can't connect a PlayStation Controller to a Nintendo Switch natively, which means you'll need a wireless adapter. As we already mentioned above, we're using the 8BitDo Wireless Bluetooth Adapter, which is $19 from Amazon.

What is the default password for wago pfc100? ›

Log in with user: admin / password: wago.

Do wago connectors meet US code? ›

Other connectors that need maintenance or are assembled incorrectly can cause shocks, short circuits and other risk. This is another reason why Wago connectors are a great choice. They meet all of the NEC code requirements regarding splicing and terminating conductors.

What is the default password for powerline? ›

Open the utility, move your mouse over your powerline extender, and click the. icon that appears beside it. Enter admin (the default username and password) for both username and password, and click Login.

What is the password for wago Web browser? ›

In the dialog "Login", log in as the user "admin", password "wago".

Top Articles
Last Epoch Full Campaign Walkthrough
Final Fantasy 7 (VII) Rebirth Trophy Guide & Roadmap
Spasa Parish
Rentals for rent in Maastricht
159R Bus Schedule Pdf
Sallisaw Bin Store
Black Adam Showtimes Near Maya Cinemas Delano
Espn Transfer Portal Basketball
Pollen Levels Richmond
11 Best Sites Like The Chive For Funny Pictures and Memes
Things to do in Wichita Falls on weekends 12-15 September
Craigslist Pets Huntsville Alabama
Paulette Goddard | American Actress, Modern Times, Charlie Chaplin
Red Dead Redemption 2 Legendary Fish Locations Guide (“A Fisher of Fish”)
What's the Difference Between Halal and Haram Meat & Food?
R/Skinwalker
Rugged Gentleman Barber Shop Martinsburg Wv
Jennifer Lenzini Leaving Ktiv
Justified - Streams, Episodenguide und News zur Serie
Epay. Medstarhealth.org
Olde Kegg Bar & Grill Portage Menu
Cubilabras
Half Inning In Which The Home Team Bats Crossword
Amazing Lash Bay Colony
Juego Friv Poki
Dirt Devil Ud70181 Parts Diagram
Truist Bank Open Saturday
Water Leaks in Your Car When It Rains? Common Causes & Fixes
What’s Closing at Disney World? A Complete Guide
New from Simply So Good - Cherry Apricot Slab Pie
Drys Pharmacy
Ohio State Football Wiki
Find Words Containing Specific Letters | WordFinder®
Abby's Caribbean Cafe
Joanna Gaines Reveals Who Bought the 'Fixer Upper' Lake House and Her Favorite Features of the Milestone Project
Tri-State Dog Racing Results
Navy Qrs Supervisor Answers
Trade Chart Dave Richard
Lincoln Financial Field Section 110
Free Stuff Craigslist Roanoke Va
Wi Dept Of Regulation & Licensing
Pick N Pull Near Me [Locator Map + Guide + FAQ]
Crystal Westbrooks Nipple
Ice Hockey Dboard
Über 60 Prozent Rabatt auf E-Bikes: Aldi reduziert sämtliche Pedelecs stark im Preis - nur noch für kurze Zeit
Wie blocke ich einen Bot aus Boardman/USA - sellerforum.de
Infinity Pool Showtimes Near Maya Cinemas Bakersfield
Dermpathdiagnostics Com Pay Invoice
How To Use Price Chopper Points At Quiktrip
Maria Butina Bikini
Busted Newspaper Zapata Tx
Latest Posts
Article information

Author: Virgilio Hermann JD

Last Updated:

Views: 5972

Rating: 4 / 5 (61 voted)

Reviews: 92% of readers found this page helpful

Author information

Name: Virgilio Hermann JD

Birthday: 1997-12-21

Address: 6946 Schoen Cove, Sipesshire, MO 55944

Phone: +3763365785260

Job: Accounting Engineer

Hobby: Web surfing, Rafting, Dowsing, Stand-up comedy, Ghost hunting, Swimming, Amateur radio

Introduction: My name is Virgilio Hermann JD, I am a fine, gifted, beautiful, encouraging, kind, talented, zealous person who loves writing and wants to share my knowledge and understanding with you.